MONITOUCH
PRODUCTS SUPPORT FAQ DISTRIBUTORS COMPANY
Hakko Electronics
MONITOUCH
HOME > FAQ
FAQ
Answer for frequently asked questions about our products and troubleshooting

♦ Question
Q27  How can I check the communication conditions between the temperature controller and MONITOUCH?
♦ Answer
A27

The status of a temperature controller is output to the MONITOUCH system memory ($s).

Check the addresses below according to the ports you wish to check.   

   
   

$s730:   Status of port 0    

$s731:   Status of port 1    

$s732:   Status of port 2   

      :               :

$s761:   Status of port 31

 

 

 

     
  Temperature controller status codes   
   

Code

Description

0000H

Normal

FFFFH

Timeout

8001H

Check code error

8002H

Data error

800BH

Error code received from temperature controller